How deep does buried electrical wiring have to be in Ontario?
Burying cable or conduit in a trench — How deep does buried wiring have to be?
It depends on what you are burying (low voltage, Table 53). Cable with no metal sheath or armour — NMWU, for example — needs at least 600 mm of cover where vehicles do not travel, and 900 mm under driveways and roadways. Armoured cable (Teck, ACWU) and conduit or raceway need less: 450 mm where vehicles do not travel, and 600 mm where they do. Cover is measured from the top of the cable or conduit up to finished grade. Rule 12-012 has the rest — protection requirements and the exceptions — so check it in the code book before you rely on a shallower trench.
⚑ WATCH OUT FOR THIS
Depth is measured to the top of the cable/conduit after backfill settles — dig the trench deeper than the number, not to it.
Code book: OESC 29th ed. (2024) — Rule 12-012 & Table 53: Burial depth of cables & raceways
Help only — check the rule in the real code book before you trust it. This does not take the place of an ESA inspection.